Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 193

Rebuild the AGA Files

Follow these steps to clear all the history and event records.

1.

Set the controller into the Service mode.

2.

Select the AGA File Initialization check box.

3.

Click Set.

All the history and event records are cleared.

4.

Click Run, and exit the service mode.

Delete the DataSite Workbench Program

Follow these steps to delete the DataSite Workbench program that is on the
DataSite controller.

1.

Set the controller into the Service mode.

2.

Select the DS Workbench Initialization check box.

3.

Click Set.

The DataSite Workbench program is deleted from the DataSite
controller.

4.

Click Run, and exit the service mode.

Clear the DNP3 Parameters

Follow these steps to clear the values of the DNP3 parameters.

1.

Set the controller into the Service mode.

2.

Select the DNP3 Initialization check box.

3.

Click Set.

The DNP3 parameter settings are deleted from the DataSite controller.

4.

Click Run, and exit the service mode.