DataSite Configuration Settings Utility (DS Settings) 95

See

Display the Default Settings on page 28

for the default values of the

controller communication parameters.

Reset the Register Values

Follow these steps to reset the register values in the controller to 0.

1.

Set the controller into the Service mode.

2.

Select the Register Initialize check box.

3.

Click Set.

All settings will be downloaded into the controller.

4.

Click Run, and exit the local connection.

Reset the DNP3 Parameters

Follow these steps to reset all the DNP3 parameters to their default values.

1.

Set the controller into the Service mode.

2.

Select the DNP3 Initialize check box.

3.

Click Set.