92 DataSite Configuration Settings Utility (DS Settings)

Initialize the Controller

Use the Controller Initialize function to initialize the DataSite controller.

Open the Controller Initialize Dialog Box

Follow this step to open the Controller Initialize dialog box.

From the Tools menu, choose Controller Initialize.

The Controller Initialize dialog box appears.

Switch Controller into Service Mode

To initialize the controller, you must set the controller into the Service mode
first.

Follow these steps to set the controller into the Service mode.

1.

Power down the DataSite controller.

2.

Use a serial communication cable to connect one PC serial port with the
COM2 of the controller.

IMPORTANT

Only COM2 can be used.