56 DataSite Configuration Settings Utility (DS Settings)
This table provides a description of the column headers in the HART Settings
dialog box.
Description of HART block parameters
Header
Description
NO.
Serial number of each HART scan block.
HART Channel
Channel for the HART interface module to send commands to. The
effective range is 0…2.
•The HART0 channel supports multi-branched HART scan, and the
data of up to 13 pieces of HART equipment can be scanned.
•The HART1 and HART2 channels are point-to-point scan, and not
only do they support HART protocol communication, they also
support standard 4…20 mA signals.
Address
Communication address of the HART equipment. The effective
range is 0…15.