Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 141

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 141

Signal Addresses

You need to enter the addresses for the static pressure (P), temperature (T),
and differential pressure (DP) signals. These are the signals you have
connected using the Analog In (AI) and/or HART channels during the setup
of the DataSite controller. You may choose to use these signals from the
AI0…AI5 channels on the DataSite controller. For more information on the
wiring channel of each field signal, refer to I/O Wiring in the DataSite
Electronic Flow Meter and Remote Terminal Unit Hardware User Manual,
publication 1758-UM001.

Data Type

For each signal address, select its data type.

UShort: Unsigned short

Float: Floating point

k and b

The linear slope k and constant b are calculated using the engineering
calibration range shown in the following table.

Hi: the maximum engineering value range of the instrument connected
with the AI channel.

Lo: the minimum engineering value range of the instrument connected
with the AI channel.

These are the default ranges for each signal.

DP: 0…150 in H

2

O of 60 ºF

P: 0…1500 psia

T: 0…150 ºF

Input

Address

Data
Type

Data

k

b

AI0

30001

USHORT 1000…50000 Sampled processed value

(Hi-Lo)/(50000-10000) Lo-10000*k

AI1

30002

USHORT 1000…50000 Sampled processed value

(Hi-Lo)/(50000-10000) Lo-10000*k

AI2

30003

USHORT 1000…50000 Sampled processed value

(Hi-Lo)/(50000-10000) Lo-10000*k

AI3

30004

USHORT 1000…50000 Sampled processed value

(Hi-Lo)/(50000-10000) Lo-10000*k

AI4

30005

USHORT 1000…50000 Sampled processed value

(Hi-Lo)/(50000-10000) Lo-10000*k

AI5

30006

USHORT 1000…50000 Sampled processed value

(Hi-Lo)/(50000-10000) Lo-10000*k

Advertising