Extension Modbus Protocol for DataSite Controllers (1758-FLO) 295

There is no event code for command number 14.

Command Number 15: Set the Alarm Range of Input Parameters

Use command number 15 to set the upper and lower alarm limits and alarm
dead-band of static pressure, temperature, and differential pressure or pulse.

49041

u_short

R

Address of pressure

49042

u_short

R

Data type of pressure
0: u_short
1: float

49043

float

R

k factor of pressure

49045

float

R

b factor of pressure

49047

u_short

R

Address of temperature

49048

u_short

R

Temperature data type
0: u_short
1: float

49049

float

R

k factor of temperature

49051

float

R

b factor of temperature

Return codes for command number 14

Return Code

Description

00

OK

01

Meter run is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 15

Address

Data Type

Attribute

Description

49025

u_short

RW

15

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

W

Enable or disable differential
pressure or pulse alarm
0: Disable
1: Enable

Parameters for command number 14 (Continued)

Address

Data Type

Attribute

Description