Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 217

Return register

+0, 2 = device specific status, 8-bit unsigned integer

+3 = Operational modes, 8-bit unsigned integer

+4, 5 = Analog outputs saturated, 24-bit unsigned integer

+6, 7 = Analog outputs fixed, 24-bit unsigned integer

+8, 13 = Device-specific status, 8-bit unsigned integer

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

54

Purpose

Read Transmitter Variable Information

Send register

+0 = Code for transmitter variable to be zeroed, 8-bit unsigned
integer

Return register

+0 = Return code for transmitter variable to be zeroed, 8-bit
unsigned integer

+1, 2 = Transmit variable sensor serial number, 24-bit unsigned
integer

+3 = Transmit variable limits units code, 8-bit unsigned integer

+4, 5 = Transmit variable upper limit (float point)

+6, 7 = Transmit variable lower limit (float point)

+8, 9 = Transmit variable damping value (seconds) (float point)

+10, 11 = Transmit variable minumum span (float point)

Unit register

+0 = Transmit variable code, 8-bit unsigned integer

+1 = Transmit variable limits units code, 8-bit unsigned integer

HART state register

+0 = state 0

+1 = state 1

Command

59

Purpose

Write Number of Responses Preambles

Send register

+0 = Number of preambles to be sent with the Response message
from the Slave to the Master, 8-bit unsigned integer, between 5
and 20

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Description of HART commands (Continued)