268 Extension Modbus Protocol for DataSite Controllers (1758-FLO)

Modbus Register Range

The registers used in the DataSite controller include four types of I/O
registers.

Coil registers

Coil registers are single-bit registers located in the digital output section of the
I/O database. There are 4096 coil registers numbered from 00001 to 04096.

State registers

State registers are single registers located in the digital input section of the I/O
database. There are 4096 state registers numbered 10001 to 14096.

Input registers

Input registers are 16-bit registers located in the analog section of the I/O
database. There are 4096 registers numbered 30001 to 34096.

Hold registers

Hold registers are 16-bit registers located in the analog output section of the
I/O database. There are 9999 hold registers numbered 40001 to 49999.

Modbus register range

Type

Range

Number of
Registers

Attribute

Coil Registers

1…4096

4096

RW

State Registers

10001…14096

4096

RO

Input Registers

30001…34096

4096

RO

Hold Registers

40001…49999

9999

RW