196 DataSite Flow Configuration Utility (DS FloConfig)

Configure the Scan Settings

For integrated modules such as the DataSite controller, the master ports can
directly read/write parameters by accessing the fixed Modbus registers. We
need to set scan blocks of US1 and US2 only when we want to access other
pieces of equipment connected with the two serial ports (COM1, COM2).

Use Scan Settings to match the register addresses of the 1758 controller with
those of the serially connected equipment.

Understand the Scan Blocks

Every scan block corresponds to a scan task. The maximum number of scan
tasks is 128. This table lists the description of each item in a scan block.

Block Type

The block type indicates the category of scan block data.

Scan block parameters and their descriptions

Scan Block Parameter

Description

Block type

Scan block data category

Address

Modbus slave station number of serial communication
equipment connected with COM1 or COM2.

Signal type

Signal register category

Scan time

Read/Write interval

Master Register

Register address where data is saved in the controller,
decided by the user.

Slave Register

You can set the read/write data register address of the
slave communication equipment according to the parameter
form of the slave communication equipment register.

Reg_Num

The number of read/write data registers.

Err_Cnt

The number of times the scan block fails to communicate.

Err_State

Scan block communication state.
If the Err_State value is 1, it means the communication has
failed. A value of 0 indicates that the communication is OK.

Remark

User comments.
You can enter a note or a tip for the scan block. Note that
this field will not be downloaded to the DataSite controller.

Scan block types and their descriptions

Name

Function

US1 block

1758-RTU controller Read-write data of the serial
equipment connected with the serial port COM1.

US2 block

1758-RTU controller Read-write data of the serial
equipment connected with the serial port COM2.