Reset the communication parameters – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 189

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 189

7.

To exit the Test Communication state, power the DataSite controller off
and on again.

Normal communication with the controller is resumed.

Reset the Communication Parameters

The following tables show the default values of the COM1, COM2 and
Ethernet communication parameters:

Default values of COM1, COM2 communication parameters

Parameter Name

Default Value

Station

1

Protocol

Modbus RTU

Master/Slave State

Slave

Duplex

Full

Baud rate (bps)

9600

Parity

None

Data bits

8 bits

Stop bits

1 bit

Port type

RS232

Timeout (10 ms)

100

Delay time (10 ms)

0

Default values of Ethernet communication parameters

Parameter Name

Default Value

IP

192.168.100.75

Mask

255.255.255.0

Gateway

192.168.100.1

Port

502