Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 59

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

DataSite Configuration Settings Utility (DS Settings) 59

If the number of registers is 0 in any command, you do not have to enter a
register address.

The register range is 40003…49999 for 1758-RTU controllers, and
40003…47999 for 1758-FLO controllers.

Description of HART Commands

The following table provides a description of each HART command and the
registers that it uses.

48

Read additional Transmitter Status

0

13

0

2

54

Read Transmitter Variable Information

1

10

2

2

59

Write Number Of Response Preambles

1

0

0

2

Number of registers used in each HART command (Continued)

Command

Description

Number of registers

Send register

Return register Unit register

HART state
register

Description of HART commands

Command

0

Purpose

Read the equipment identifier.
This command must be configured for each HART device in order
for the other commands to work.

Send register

Not used

Return register

+0 = manufacturer ID code, 8-bit unsigned integer

+1 = manufacturer equipment type code, 8-bit unsigned integer

+2 = forerunner character number, 8-bit unsigned integer

+3 = global command revision level, 8-bit unsigned integer

+4 = transmitter revision level, 8-bit unsigned integer

+5 = software revision level, 8-bit unsigned integer

+6 = hardware revision level, 8-bit unsigned integer

+7 = equipment function flags, 8-bit unsigned integer

+8, 9 = Device Identification Number (double), 24-bit unsigned
integer

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

1

Purpose

Read primary variable (P. V.)

Send register

Not used

Return register

+0, 1 = P. V. (float point)