Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 216

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

216 DataSite Flow Configuration Utility (DS FloConfig)

HART state register

+0 = state 0

+1 = state 1

Command

35

Purpose

Write Primary Variable Range Values

Send register

+0 = Primary Variable 0 code, 8-bit unsigned integer

+1, 2 = Primary Variable upper range value (float point)

+3, 4 = Primary Variable lower range value (float point)

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

38

Purpose

Reset Configuration Changed Flag

Send register

Not used

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

40

Purpose

Enter/Exit Fixed Primary Variable Current Mode

Send register

+0, 1 = Actual fixed Primary Variable current level, units of
milliamperes (float point)

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

44

Purpose

Write Primary Variable Units

Send register

+0 = Primary Variable units code, 8-bit unsigned integer

Return register

Not used

Unit register

Not used

HART state register

+0 = state 0

+1 = state 1

Command

48

Purpose

Read Additional Transmitter Status

Send register

Not used

Description of HART commands (Continued)