Clear error codes – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 90

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

90 DataSite Configuration Settings Utility (DS Settings)

All the states of controller are showed by a 16-bit code. For details, see the
following tables.

If more than one error occurs, an "OR" operation will be performed on the
codes. For example, if both US1 and US2 communication errors occur, the
error code will be 0600. If all errors occur, the code will be 0703.

If more than one initialization state exists, an "OR" operation will be
performed on the codes. For example, a code of 0x0102 means that test
communication and initialization of communication parameters are in
progress.

Clear Error Codes

Follow this step to clear the error codes of the controller.

Click Clear Error

Error codes

Error Code

Meaning

0x0001

Hardware register error

0x0002

Data FLASH error

0x0100

HART communication error

0x0200

US1 communication error

0x0400

US2 communication error

Initialization state codes

Initialization State Code

Meaning

0x0001

Test communication.

0x0002

Initialize communication parameters.

0x0004

Clear the DataSite Workbench application.

0x0008

Initialize registers.

0x0100

Initialize file system.

0x0200

Initialize DNP3.

DS Workbench Status codes

DS Workbench Status Code

Meaning

0001

DataSite Workbench is running.

0000

DataSite Workbench is stopped.