274 Extension Modbus Protocol for DataSite Controllers (1758-FLO)

Modbus Registers for Flow Configuration Parameters (RO)

Modbus addresses for flow configuration parameters

Meter Run

Starting Address

Parameter
Address

Address Number

0

32101

X

100

1

32201

X + 100

100

2

32301

X + 200

100

3

32401

X + 300

100

4

32501

X + 400

100

5

32601

X + 500

100

6

32701

X + 600

100

7

32801

X + 700

100

Flow configuration parameters

Parameter Name

Description

Data Type

Modbus Address
of Meter Run 0 = X

Enable

Bit 0: Enable calculation
Bit 1: Enable accumulation
Bit 2: Parameter modification flag
Bit 3: Type of measurement unit. 0: imperial, 1: metric
Bit 4: Flag for usage of the automatic component analysis
instrument

u_short

32101

CalInterval

Calculation interval

u_short

32102

piInterval

BMP (base multiplier period)

u_short

32103

dp_DPoint

Data point configuration (differential pressure address or pulse)

u_short

32104

p_DPoint

Data point configuration (static pressure address)

u_short

32105

t_DPoint

Data point configuration (temperature address)

u_short

32106

usAGA_Type

AGA calculation method.
0: AGA3, 1: AGA7

u_short

32107

usTapLocation

Tap location
0: Upstream, 1: Downstream

u_short

32108

usPressType

Pressure type
0: Gauge, 1: Absolute

u_short

32109

usZ_mode

AGA8 methods
0: Gas analysis, 1: HV-GR-CO2, 2: GR-CO2-N2

u_short

32110

usOrifice_Type

Orifice material
0: Type 304 and 316 stainless steel, 1: Monel, 2: Carbon steel

u_short

32111

usPipe_Type

Tube material
0: Type 304 and 316 stainless steel, 1: Monel, 2: Carbon steel

u_short

32112

usGr_Type

AGA8 relative density condition type
0: Real, 1: Ideal

u_short

32113