Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 87

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

DataSite Configuration Settings Utility (DS Settings) 87

The Add Register dialog box appears.

3.

In the Start_Addr text box, enter the address for the register.

4.

In the Reg_Cnt text box, enter the number of registers you want to add.

If you are adding more than one register, the Start_Addr value will be
the address for the first register. Subsequent registers will have
consecutive addresses.

5.

From the Type pull-down menu, select a register type from the
following options:

Unsigned

16 bit unsigned int

Signed

16 bit signed int

Float Point

32 bit float number

Hexadecimal

Hexadecimal form

Binary

binary form

ASCII

ASCII code form

BOOL

BOOL type

If the selected register type does not map to Start_Addr, this error
message appears. Click OK and reselect the register type.

6.

Click Add.

If the register address you entered is invalid, this error message appears.
Click OK and re-enter the register address.

Advertising