Command number 27: read new event logs – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 317

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 317

There is no event code for command number 26.

Command Number 27: Read New Event Logs

Use command number 27 to read the new event records. The value in register
49030 indicates how many new event records have been loaded with this
reading. The maximum number is 20. Each new event record consists of 10
registers and has the same format as an event.

49195…49204

See above

See above

Event 17

49205…49214

See above

See above

Event 18

49215…49224

See above

See above

Event 19

49225…49234

See above

See above

Event 20

Return codes for command number 26

Return Code

Description

00

OK

01

Event start index is invalid

02

Event numbers is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 27

Address

Data Type

Attribute

Description

49025

u_short

RW

27

49026

u_short

R

Return code
0: OK

49027

u_short

W

Reserved

49028

u_int

W

Pass code for user

49030

u_short

R

Number of read records

49031

u_short

R

Number of remaining new records

49032

u_short

R

Number of lost records

49033…49034

Reserved

Registers for events 2…20 (Continued)

Address

Data Type

Attribute

Description

Advertising