Extension Modbus Protocol for DataSite Controllers (1758-FLO) 297

Command Number 16: Read the Alarm Range of Input Parameters

Use command number 16 to read the upper and lower alarm limits and alarm
dead-band of static pressure, temperature, and differential pressure or pulse.

Parameters for command number 16

Address

Data Type

Attribute

Description

49025

u_short

RW

16

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

R

Whether the alarm for differential
pressure or pulse is enabled
0: Disable
1: Enable

49036

float

R

Upper alarm limit of differential
pressure or pulse

49038

float

R

Lower alarm limit of differential
pressure or pulse

49040

float

R

Alarm dead-band of differential
pressure or pulse

49042

u_short

R

Whether the alarm for static
pressure is enabled
0: Disable
1: Enable

49043

float

R

Upper alarm limit of static
pressure

49045

float

R

Lower alarm limit of static
pressure

49047

float

R

Alarm dead-band of static
pressure

49049

u_short

R

Whether the alarm for
temperature is enabled
0: Disable
1: Enable

49050

float

R

Upper alarm limit of temperature

49052

float

R

Lower alarm limit of temperature

49054

float

R

Alarm dead-band of temperature