Command number 3: set the device name, Command number 4: read the device name – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 285

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 285

Command Number 3: Set the Device Name

Use command number 3 to set the device name of the 1758-FLO DataSite
controllers. The maximum string length is eight characters.

There is no event code for command number 3.

Command Number 4: Read the Device Name

Use command number 4 to read the device name of the 1758-FLO DataSite
controllers. The maximum string length is eight characters.

Parameters for command number 3

Address

Data Type

Attribute

Description

49025

u_short

RW

3

49026

u_short

R

Return code

49027

u_short

W

Reserved

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

W

Device name 1

49036

u_short

W

Device name 2

49037

u_short

W

Device name 3

49038

u_short

W

Device name 4

49039

u_short

W

Device name 5

49040

u_short

W

Device name 6

49041

u_short

W

Device name 7

49042

u_short

W

Device name 8

Return codes for command number 3

Return Code

Description

00

OK

100

Pass code is incorrect

Other

Invalid

Parameters for command number 4

Address

Data Type

Attribute

Description

49025

u_short

RW

4

49026

u_short

R

Return code

49027

u_short

W

Reserved

Advertising