246 DataSite DNP3 Configuration Utility (DS DNP3)

The following table lists the range and default value of each PC
communication parameter.

3.

From the Connect pull-down menu, select a TCP/IP or a serial (COM)
port.

If you have selected TCP/IP, skip to step 6 to configure TCP/IP port
settings.

If you have selected a COM port, continue to configure COM port
settings.

4.

Determine the parameters for the serial port of the DataSite controller
currently in use. From the Baud pull-down menu, select the baud rate
for the COM port.

5.

In the Slave box, enter the slave station number.

6.

Enter the IP address and communication port number.

7.

In the Delay Time box, enter the duration, in milliseconds, for the delay
time. Maximum delay time allowed is 1 s (or 1000 ms).

8.

In the Timeout box, enter the duration, in milliseconds, for the timeout.
Maximum timeout allowed is 10 s (or 10000 ms).

Value ranges of PC communication parameter

Variable

Range

Default Value

Connect

TCP/IP, COM1…COM9

TCP/IP

Baud

2400, 4800, 9600, 38400, 57600

9600

Slave

1…247

1

IP

xxx.xxx.xxx.xxx

192.168.100.75

Port

5…65535

502

Delay Time

10…1000

10

Timeout

1000…10000

1000