Command number 23: get hourly history – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 311

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 311

Command Number 23: Get Hourly History

Use command number 23 to get hourly history data.

Parameters for command number 23

Address

Data Type

Attribute

Description

49025

u_short

RW

23

49026

u_short

W

Return code
0: OK

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030

u_short

W

Start date index (0…35).
0: Today
1: Yesterday

49031

u_short

W

Start hour index in the day
(0…23, 24…29)

49032

u_short

W

Number of records you want to
get. The maximum value is 8.

49033…49034

Reserved

Registers for record 1 of hourly history data

Address

Data Type

Attribute

Description

49035

u_char[0]

R

Year (storage time)

u_char[1]

Month (storage time)

49036

u_char[0]

R

Day (storage time)

u_char[1]

Hour (storage time)

49037

u_char[0]

R

Minute (storage time)

u_char[1]

Second (storage time)

49038

u_short

R

Unit of measurement
0: U.S.
1: Metric

49039

float

R

Average static pressure

49041

float

R

Average temperature

49043

float

R

Average differential
pressure/average pulse

49045

float

R

Density

49047

float

R

Accumulated run time

49049

float

R

Hourly base volume of flow rate

49051

float

R

Hourly flowing volume of flow
rate

49053

float

R

Hourly mass volume of flow rate