Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 273

Modbus addresses for calculation results block 2

Meter Run

Starting Address

Parameter
Address

Address Number

0

33101

X

50

1

33151

X + 50

50

2

33201

X + 100

50

3

33251

X + 150

50

4

33301

X + 200

50

5

33351

X + 250

50

6

33401

X + 300

50

7

33451

X + 350

50

Parameters in calculation results block 2

Parameter Name

Description

Data Type

Modbus Addresses
for Meter Run 0
Parameters (= X)

qeh_pval

Energy hour flow rate

float

33101…33102

qe_yesterday

Energy flow of the previous day

float

33103…33104

avh_EXT

Hourly average of the square root of the product of static pressure and
differential pressure. This is also the average uncorrected volume
(AGA7) for the hour.

float

33105…33106

avd_EXT

Daily average of the square root of the product of static pressure and
differential pressure. This is also the average uncorrected volume
(AGA7) for the day.

float

33107…33108

avh_Gr

Average real relative density for the hour

float

33109…33110

avd_Gr

Average real relative density for the day

float

33111…33112

Y2

Expansion fsactor based on the absolute static pressure measured at
the downstream tap

float

33113…33114

Reserved

Reserved

float

33115…33150