Publication 1758-UM002D-EN-P - October 2010

DataSite Flow Configuration Utility (DS FloConfig) 211

This table provides a description of the column headers in the HART Settings
dialog box.

Description of HART block parameters

Header

Description

NO.

Serial number of each HART scan block.

HART Channel

Channel for the HART interface module to send commands to. The
effective range is 0…2.

•The HART0 channel supports multi-branched HART scan, and the

data of up to 13 pieces of HART equipment can be scanned.

•The HART1 and HART2 channels are point-to-point scan, and not

only do they support HART protocol communication, they also
support data collection of 4…20 mA signals.

Address

Communication address of the HART equipment. The effective
range is 0…15.

Command

HART command to be sent to the HART equipment. The effective
value of each HART command is as follows:

•Read Unique Identifier: 0

•Read Primary Variable:1

•Read P. V. Current And Percent Of Range: 2

•Read Dynamic Variable And P. V. Current: 3

•Read Transmitter Variables: 15

•Read Primary Variable Output Information: 33

•Reset Configuration Changed Flag: 38

•Read additional Transmitter Status: 48

•Read Transmitter Variable Information: 54

Scan Time

Time cycle of scanning HART equipment data.
Effective range is 50 ms…450 hours.

Send Register

Register for storing command data.
Effective range is 40003…49999 for 1758-RTU controllers and
40003…47999 for 1758-FLO controllers.

Return Register

Register for storing command response data.
Effective range is 40003…49999 for 1758-RTU controllers and
40003…47999 for 1758-FLO controllers.

Unit Register

Register for storing the unit of HART equipment data returned.
Effective range is 40003…49999 for 1758-RTU controllers and
40003…47999 for 1758-FLO controllers.