Command number 10: read the input signal test – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 290

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

290 Extension Modbus Protocol for DataSite Controllers (1758-FLO)

There is no event code for command number 9.

Command Number 10: Read the Input Signal Test

Use command number 10 to read the signal test settings and test values.

Return Codes for Command number 9

Return Code

Description

00

OK

01

Meter run is invalid

02

The value for differential pressure or pulse tested is invalid

03

The value for static pressure tested is invalid

04

The value for temperature tested is invalid

100

Pass code is wrong

Other

Invalid

Parameters for command number 10

Address

Data Type

Attribute

Description

49025

u_short

RW

10

49026

u_short

R

Return code

49027

u_short

W

Meter run (0…7)

49028

u_int

W

Pass code for user

49030…49034

Reserved

49035

u_short

R

Whether differential pressure or
pulse is tested.
0: No test
1: Test

49036

u_short

R

Whether static pressure is tested.
0: No test
1: Test

49037

u_short

R

Whether temperature is tested.
0: No test
1: Test

49038

float

R

Test value for differential pressure
or pulse

49040

float

R

Test value for static pressure

49042

float

R

Test value for temperature