Page 296

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

296 Extension Modbus Protocol for DataSite Controllers (1758-FLO)

There is no event code for command number 15.

49036

float

W

Upper alarm limit of differential
pressure or pulse

49038

float

W

Lower alarm limit of differential
pressure or pulse

49040

float

W

Alarm dead-band of differential
pressure or pulse

49042

u_short

W

Enable or disable static pressure
alarm
0: Disable
1: Enable

49043

float

W

Upper alarm limit of static
pressure

49045

float

W

Lower alarm limit of static
pressure

49047

float

W

Alarm dead-band of static
pressure

49049

u_short

W

Enable or disable temperature
alarm
0: Disable
1: Enable

49050

float

W

Upper alarm limit of temperature

49052

float

W

Lower alarm limit of temperature

49054

float

W

Alarm dead-band of temperature

Return codes for command number 15

Return Code

Description

00

OK

01

Meter run is invalid

02

The input value for differential pressure or pulse alarm setting is
invalid

03

The input value for static pressure alarmsetting is invalid

04

The input value for disable temperature alarmsetting is invalid

100

Pass code is incorrect

Other

Invalid

Parameters for command number 15 (Continued)

Address

Data Type

Attribute

Description