Publication 1758-UM002D-EN-P - October 2010

Extension Modbus Protocol for DataSite Controllers (1758-FLO) 269

Modbus Registers for Physical I/O Hardware

All of the I/O hardware that is used by the DataSite controller must be
assigned to I/O database registers in order for the I/O points to be accessed.
They are mapped as below.

Modbus addresses for I/O hardware

Name

Data Type

Modbus Address

Attribute

DI0

BOOL

10001

RO

DI1

BOOL

10002

RO

DI2

BOOL

10003

RO

DI3

BOOL

10004

RO

DI4

BOOL

10005

RO

DI5

BOOL

10006

RO

DI6

BOOL

10007

RO

DI7

BOOL

10008

RO

DI8

BOOL

10009

RO

DI9

BOOL

10010

RO

DI10

BOOL

10011

RO

DO0

BOOL

1

RW

DO1

BOOL

2

RW

DO2

BOOL

3

RW

DO3

BOOL

4

RW

AI0

U_SHORT

30001

RO

AI1

U_SHORT

30002

RO

AI2

U_SHORT

30003

RO

AI3

U_SHORT

30004

RO

AI4

U_SHORT

30005

RO

AI5

U_SHORT

30006

RO

AI6

U_SHORT

30007

RO

AI7

U_SHORT

30008

RO

AO0

U_SHORT

40001

RW

AO1

U_SHORT

40002

RW

PI0

U_INT

30011…30012

RO

PI1

U_INT

30013…30014

RO

PI2

U_INT

30015…30016

RO