Register addresses, 1758-flo datasite variables, Register addresses 1758-flo datasite variables – Rockwell Automation 1758-RTU202 DataSite Software User Manual FRN 1.2 User Manual

Page 324

Advertising
background image

Publication 1758-UM002D-EN-P - October 2010

324 Enron Modbus Protocol for the 1758-FLO DataSite Controller

Register Addresses

The following table lists the address ranges of the Enron registers that hold
short integers, long integers, and single precision floats.

1758-FLO DataSite
Variables

A 1758-FLO DataSite controller supports up to eight meter runs.
Meter runs are configured individually. Gas quality is set for each meter run.
The following table lists the ranges of Enron Modbus variables used by the
controller.

Register address ranges

Range

Data Type

Description

32

Record

Event/Alarm archive
(Event from 1…700, alarm from 701…1000)

701…716

Record

Hourly/Daily archive

1001…2999

Boolean

Reserved

3001…3450

Short integer

16 bits, high byte first

5001…5080

Long integer

32 bits, high byte fist, high word first. For example,
if the number 2,923,517,522 sent a 32-bit
unsigned integer, it would be AE 41 56 52.

7001…7800

Float

32 bits, IEEE single precision floating-point
number, high byte first, high word first. For
example, if the number 326,787 is sent as a 32-bit
float, it would be 48 9F 90 60.

Enron Modbus variable ranges

Purpose

Hourly/Daily Archive

Boolean

Short Integer

Long Integer

Floating Point

System variables

None

None

3000…3050

None

None

Meter run 0

701…702

None

3051…3100

5001…5010

7001…7100

Meter run 1

703…704

None

3101…3150

5011…5020

7101…7200

Meter run 2

705…706

None

3151…3200

5021…5030

7201…7300

Meter run 3

707…708

None

3201…3250

5031…5040

7301…7400

Meter run 4

709…710

None

3251…3300

5041…5050

7401…7500

Meter run 5

711…712

None

3301…3350

5051…5060

7501…7600

Meter run 6

713…714

None

3351…3400

5061…5070

7601…7700

Meter run 7

715…716

None

3401…3450

5071…5080

7701…7800