Publication 1758-UM002D-EN-P - October 2010

164 DataSite Flow Configuration Utility (DS FloConfig)

Insert an Alarm Configuration

Follow these steps to insert an alarm configuration block.

1.

In the Alarm Config dialog box, click Insert.
You can also double-click any blank row indexed 24…63 in the Alarm
Config dialog box.

The Alarm Configuration dialog box appears.

2.

In the Alarm Configuration dialog box, enter the register address of the
variable, and the values for Hi Limit, Lo Limit and Dead Band.

For more information on the variables, see

Delete an Alarm

Configuration

.

3.

Select the Enable check box.

4.

Click OK.