68 DataSite Configuration Settings Utility (DS Settings)

Insert a HART Scan Block

Follow these steps to insert a HART scan block.

1.

In the HART Settings dialog box, select the row where you want to
insert the scan block to and click Insert. Alternatively, you can
double-click the row.
Note that you cannot insert data after an empty data block.

An Invalid scan block is inserted.

2.

Double-click the block to edit.

Second byte - when unused

Bit

Description

7

All bits 0 (when a communication error is reported in
the first byte).

6

5

4

3

2

1

0

Second byte - Field Device Status

Bit

Value

Description

7

hex 80

Field device malfunction

6

hex 40

Configuration changed

5

hex 20

Cold start

4

hex 10

More status available

3

hex 08

Analog output current fixed

2

hex 04

Analog output saturated

1

hex 02

Nonprimary variable out of limits

0

hex 01

Primary variable out of limits