Sigma II Indexer User’s Manual

Program Table Mode (Mode 0)

5-51

Event

Event Condition
Sets condition for execution of next program step, either repeat same program step (LOOP) or go to next
program step (NEXT) each time the event condition is satisfied (true).
Conditions:

I

/INPOSITION active

N

NEAR active

The following parameters are used to set the timing for the INPOSITION and NEAR signals.

Parameter

Signal

Settings (reference units)

Default

Pn821

/INPOSITION Signal Width Setting Range: 0~99999

1

Pn822

Near Signal Width

Setting Range: 0~99999

1

Generally set the Near width higher than the /INPOSITION width.
The /INPOSITION output signal is dependent on the logic of the /INPOSITION width and DEN. The
near signal turns on by the near width only.
See also 5.3.6 Using the /INPOSITION Output Signal.

D

DEN active (commanded position complete). DEN = distribution end.

SELx, x=0~6

Input signal (/SEL0~/SEL6) active

Tn,n=0~99999

Time [ms] from start of program step.

:

Uses same event condition as the previous program step.

Note: I, N, D, SELx can be combined with Tn. Program waits the reserved time after event condition is
satisfied (true) before execution of next program step.

ITn

Program waits n ms (Tn) after /INPOSITION becomes active before next program step.

NTn

Program waits n ms (Tn) after NEAR becomes active before next program step.

DTn

Program waits n ms (Tn) after DEN becomes active before next program step.

SELxTn Program waits n ms (Tn) after SELx becomes active before next program step.

Setting at shipping:

IT0

See also 5.7.5 Event Condition Examples

Table 5.7: Functions of the program table

FUNCTION