Sigma II Indexer User’s Manual

Installation Site

2-3

2.2

Installation Site

Table 2.1: The following precautions apply to the installation site.

Situation

Installation Precaution

Installation in a control panel

Design the control panel size, unit layout, and cooling method so the tempera-
ture around the servo amplifier does not exceed 55°C.

Installation near a heating unit

Minimize heat radiated from the heating unit as well as any temperature rise
caused by natural convection so the temperature around the servo amplifier
does not exceed 55°C.

Installation near a source of vibration

Install a vibration isolator beneath the servo amplifier to avoid subjecting it to
vibration.

Installation at a site exposed to corro-
sive gas

Corrosive gas does not have an immediate effect on the servo amplifier, but
will eventually cause electronic components and contactor - related devices to
malfunction. Take appropriate action to avoid corrosive gas.

Other situations

Do not install the servo amplifier in hot and humid locations or locations sub-
ject to excessive dust or iron powder in the air.