Table 6.10: monitors and functions – Yaskawa Sigma II Indexer User Manual

Page 159

Advertising
background image

Sigma II Indexer User’s Manual

Serial Command Functions

6-30

PER or MON2

Position Error Monitor
[reference units]

Positive Response:
PER = + 12345678 [CR] [LF]

Negative Response: ExxE

NFB or MON3

Motor Speed Monitor
[rpm]

Positive Response:
NFB = + 12345678 [CR] [LF]

Negative Response: ExxE

NREF or MON4

Speed Reference Monitor
[rpm]

Positive Response:
NREF = + 12345678 [CR] [LF]

Negative Response: ExxE

TREF or MON5

Torque Reference Monitor
[% rated torque]

Positive Response:
TREF = + 12345678 [CR] [LF]

Negative Response: ExxE

STS or MON6

Status Flag Monitor

Positive Response:
STS = 1010101 [CR] [LF]
bit 0: 1 in INPOSITION
bit 1: 1 in NEAR
bit 2: 1 in DEN (Command Position Complete)
bit 3: 1 in HOLD or Program Interruption
bit 4: 1 in Program Operation in Progress
bit 5: 1 in Current Limitation
bit 6: 1 when Main Power ON
Note: Response sent as characters, not as one byte.

PFB or MON7

Current Motor (actual) Position Moni-
tor
[reference units]

Positive Response:
PFB = + 12345678 [CR] [LF]

POS or MON8

Target Position Monitor
[reference units]

Positive Response:
POS = + 12345678 [CR] [LF]

When using an incremental position reference, monitor shows
target position (absolute position from 0).

DST or MON9

Target Distance Monitor
[reference units]

Positive Response:
DST = + 12345678 [CR] [LF]

When using an incremental position reference, monitor shows
reserved relative distance.

RPOS or MON10

Registration Target Position Monitor
[reference units]

Positive Response:
RPOS = + 12345678 [CR] [LF]

RDST or MON11

Registration Target Distance Monitor
[reference units]

Positive Response:
RDST = 12345678 [CR] [LF]

Table 6.10: Monitors and Functions

Serial Command

Function / Description

Answer