Sigma II Indexer User’s Manual

Sequence I/O Signals

5-15

5.3.1 Using the Servo ON Input Signal

The basic use and wiring procedure for the Servo ON (/S-ON) input signal
(sequence input signal) is described below. Use this signal to forcibly turn OFF the
servomotor from the host controller.

This signal is used to turn the servomotor ON and OFF.

The following parameter is used to set the state of the /S-ON signal.

o

Input /S-ON CN1-40

Servo ON

CN1-40
State

Status

Result

ON

Input Closed

Turns ON the servomotor: operates according
to signal input.
This is the default state.

OFF

Input Open

Servomotor cannot operate.
Do not turn OFF the servomotor while it is
operating except in an emergency.

Do not use the Servo ON (/S-ON) signal to start or stop the motor. Doing so will shorten
the life of the servo amplifier. Always use a stop input or command to start or stop the
servomotor.

Parameter

Signal

Pin No.

Setting

Default

Pn80B

/S-ON

CN1-40

0 = Input Signal Closed
= Servo ON
1 = Input Signal Open
= Servo ON
2 = Always Servo ON
3 = Always Servo OFF

0

+24V

CN1-47

CN1-40

7mA

0V

Servo amplifier

I/O power supply

Photo
coupler

Host controller

/S-ON

+24V

IN

3.3k

:

CAUTION