Yaskawa Sigma II Indexer User Manual
Page 82

Sigma II Indexer User’s Manual
Using the Encoder Signal Output
5-27
Divided encoder signals are output.
The dividing ratio setting is not related to the gear ratio setting (Pn202 and 203) for
setting reference units.
Note: Dividing means converting an input pulse train from the encoder mounted on the servomotor accord-
ing to the preset pulse density and outputting the converted pulse. The units are pulses per revolution
(ppr).
Output Phase Form
SG: Connect to 0V on the position counter.
Pulse Divider Setting
Set the pulse dividing ratio in the following parameter.
Set the number of pulses for PG output signals (PAO, /PAO, PBO, /PBO).
Pulses from the servomotor encoder (PG) are divided by the preset number before
being output.
The number of output pulses per revolution is set at this parameter.
Output
o
SG CN1-1
Signal ground
Parameter
Signal
Setting
(p/rev)
Pn201
PG Divider
Range: 16 to 16384
Default Setting: 16384
Forward
rotation
Reverse
rotation
Phase A
Phase C
t
t
Phase A
Phase B
Phase B
Phase C
90°
90°
Output terminals: PAO (CN1-33)
/PAO (CN1-34)
PBO (CN1-35)
/PBO (CN1-36)
Phase A
Phase B
Output
Servo Amplifier
Servomotor
encoder
Serial
data
PG
Frequency
division