5 using the warning output signal – Yaskawa Sigma II Indexer User Manual

Page 76

Advertising
background image

Sigma II Indexer User’s Manual

Sequence I/O Signals

5-21

This signal indicates that the servo amplifier has completed all preparations and is
ready to receive the Servo ON signal.

The following parameter is used to set the state of the /S-RDY output.

5.3.5 Using the Warning Output Signal

The basic use and wiring procedure for the warning (/WARN) output signal (photo-
coupler output signal) are given below.

The signal consists of the following output signals.

/WARN signals: overload, regenerative overload, low battery, and
indexer error

This output signal indicates an overload, regenerative overload warning, low battery,
or indexer error.

The following parameter is used to set the state of /WARN output.

/S-RDY
State

Status

Result (default state)

ON

Output Closed or low level.

Servomotor is ready.

OFF

Output Open or high level.

Servomotor is not ready.

Parameter

Signal

Pin No.

Setting

Default

Pn818

/S-RDY

CN1-29, 30

0 = Output Closed = Servo ready.

1 = Output Open = Servo ready.

0

/WARN CN1-25, 26

Warning Output Signal

/WARN
State

Status

Result (default state)

ON

Output Closed or low level.

Error warning. (overload, regenerative over-
load, low battery, and indexer error).

OFF

Output Open or high level.

Normal operation. No warning.

Parameter

Signal

Pin No.

Setting

Default

Pn816

/WARN

CN1-25, 26

0 = Output Closed = Error Warning.

1 = Output Open = Error Warning.

0

+24V

0V

Servo amplifier

I/O power supply

Photocoupler output levels
per output node:
• Maximum operating volt-

age: 30V

DC

• Maximum output current:

50mA

DC

CN1-25 /WARN+

CN1-26 /WARN-

Output

o

Advertising