11 homing / jog speed table mode (mode 1), 1 homing /jog mode setting, 2 homing / jog speed table inputs setting – Yaskawa Sigma II Indexer User Manual

Page 124

Advertising
background image

Sigma II Indexer User’s Manual

Homing / Jog Speed Table Mode (Mode 1)

5-69

5.11 Homing / Jog Speed Table Mode (Mode 1)

5.11.1 Homing /Jog Mode Setting

Set the /MODE 0/1 input signal to Mode 1 for Homing / Jog Speed table mode. The
following parameter is used for defining the /MODE 0/1 input signal.

5.11.2 Homing / Jog Speed Table inputs Setting

The following parameters are used to define the input signals used in homing and jog
speed table (Mode 1).

Table 5.18:

PARAMETER

SIGNAL

PIN No.

SETTING

DEFAULT

Pn803

MODE0/1

CN4-3

0 = Input Signal Closed = Mode 0
1 = Input Signal Open = Mode 0
2 = Always Mode 0
3 = Always Mode 1

0

Table 5.19:

PARAMETER

SIGNAL

PIN No.

SETTING

DEFAULT

Pn804

/HOME

CN4-5

0 = Input Signal Closed = Homing Start
1 = Input Signal Open = Homing Start
2 or 3 = No Homing

0

Pn80E

/DEC

CN1-44

0 = Close = Zero-point Deceleration LS
1 = Open = Zero-point Deceleration LS
2 = Always = Zero-point Deceleration LS
3 = No Zero-point Deceleration LS

0

Pn805

/JOGP

CN4-7

0 = Input Signal Closed = Jog Forward
1 = Input Signal Open = Jog Forward
2 or 3 = No Jog Forward

0

Pn806

/JOGN

CN4-9

0 = Input Signal Closed = Jog Reverse
1 = Input Signal Open = Jog Reverse
2 or 3 = No Jog Reverse

0

Advertising