Sigma II Indexer User’s Manual

Setting up the Reference Units

5-33

The following parameter is used to set the default positioning and registration speed if no
speed is specified during program execution while in serial mode.

5.5.3 Setting the Acceleration / Deceleration Rate [x 1000 Reference Units/
min/ms]

The Sigma II Indexer stores the acceleration and deceleration data in units of [X1000 Refer-
ence Units/min/ms].

Determine load (workpiece) acceleration or deceleration in terms of 1,000 reference
units per minute per millisecond.

Example:

Reference unit = 0.01 mm
Desired acceleration is 0.1 second from 0 to 15 m/min:

Acceleration = 15 [x1000 reference units/min/ms]

The following parameters are used to set the acceleration and deceleration rate.

Parameter

Signal

Setting [x1000 ref. units/min]

Default

Pn81E

Positioning/ Registration Speed

1~99999999

1000

Parameter

Signal

Setting

Default

Pn81F

Acceleration

1~99999999 [x1000 ref. units/min/ms]

1000

Pn820

Deceleration

1~99999999 [x1000 ref. units/min/ms]

1000

Pn208

Position Reference

Movement

Averaging

Time

0~6400 [0.01 msec]

0

15,000 mm/min

0.01 mm

= 1,500,000 reference units/min.

1,500,000 ref. units/min

0.1 sec

= 15,000 reference units/min/ms

0.1 sec

100 msec

X