Homing / Jog Speed Table Mode (Mode 1)

5-70

5.11.3 Homing Routine Parameters

The following parameters are used to setup the homing routines for incremental
encoders only.

Home Position, Pn 823:

Once homing is complete, the position reference is automatically set to the value set in Pn81D.

Alarm E16A will occur if Pn81D is set outside the forward and reverse position limits, Pn81B

and Pn81C, when Pn81A=1, 2, or 3 (rotary). Refer to 5.2.2 Setting the Overtravel Limit Func-
tion.

Note:

If a homing method, Pn823 is specified, then homing must be executed before the forward and

reverse position reference limits are recognized when Pn81A=0 (linear). Refer to 5.2.2 Setting
the Overtravel Limit Function.

Pn807

/JOG0

CN4-11

0 = Input Signal Closed = Jog Select
1 = Input Signal Open = Jog Select
2 = Always Jog Select
3 = No Jog Select

0

Pn808

/JOG1

CN4-13

0

Pn809

/JOG2

CN4-15

0

Pn80A

/JOG3

CN4-17

0

Table 5.20:

PARAMETER

SETTING RANGE

UNITS

DEFAULT

Pn81D

Home Position

-99999999~ +99999999

Ref. Units

0

Pn823

Homing Method

0 = No Homing
1 = /DEC and CØ-Pulse
2= /DEC only
3= CØ-Pulse only

-

0

Pn824

Homing Direction

0 = Forward
1 = Reverse

-

0

Pn825

Homing Move Speed

0 ~ 99999999

x1000 Ref. Unit / min.

1000

Pn826

Homing Approach Speed 0 ~ 99999999

x1000 Ref. Unit / min.

1000

Pn827

Homing Creep Speed

0 ~ 99999999

x1000 Ref. Unit / min.

1000

Pn828

Homing Final

Move Distance

-99999999 ~ +99999999

Ref. Units

0

Table 5.19:

PARAMETER

SIGNAL

PIN No.

SETTING

DEFAULT