Caution – Yaskawa Sigma II Indexer User Manual

Page 48

Advertising
background image

Sigma II Indexer User’s Manual

Two-Step Trial Operation

4-3

4.1.1 Step 1: Trial Operation for Servomotor without Load

In step 1, make sure that the servomotor is wired properly as shown below. Incorrect
wiring is generally the reason why servomotors fail to operate properly during trial
operation.

z Check main power supply circuit wiring.

z Check servomotor wiring.

z Check CN1 and CN4 I/O signal wiring (if applicable).

z Check CN6 serial command wiring (if applicable).

Make sure the host device and other adjustments are completed as much as possible
in step 1 (prior to connecting the servomotor to equipment).

Do not operate the servomotor while it is connected to the equipment.

To prevent accidents, initially perform step 1 where the trial operation is conducted under no-load conditions
(with all couplings and belts disconnected).

CAUTION