4.4 MP2000 Series Machine Controller Parameter Details

4.4.2 Motion Setting Parameter Details

4-28

( 2 ) Mode Setting 1

[ a ] Continuous Latch Function of SGDV SERVOPACKs

By selecting Latch Detection Demand in the parameter RUN Command Setting (OW

00, bit 4), the Continuous

Latch Function is enabled.
This function is for SGDV SERVOPACKs, so the appropriate parameter settings must be made in the SGDV SERVO-
PACKs.

Related Parameters

• Motion setting parameters

OW

01

Mode Setting 1

Setting Range

Setting Unit

Default Value

0000H

Description

Bit 0

Excessive Deviation Error Level Setting

Set whether excessively following errors are treated as warnings or as alarms.

0: Alarm (default): Axis stops operating when an excessively following error is detected.
1: Warning: Axis continues to operate even if an excessively following error is detected.

Related Parameters
OL

22: Error Count Alarm Detection

IL

02, bit 0: Warning (Excessive deviation)

IL

04, bit 9: Alarm (Excessive deviation)

Bit 3

Speed Loop P/PI Switch

Switch the SERVOPACK’s speed loop between PI control and P control.
The setting is enabled when the move command or the SERVO ON command is sent.

0: PI control (default)
1: P control

Bit 4

Gain Switch

Switch the gain to the Second Gain set in the SERVOPACK parameters.
The setting is enabled when the move command or the SERVO ON command is sent.
There is no gain switch parameter in the Servo command option area in the SGD-N, SGDB-N, or
SGDH+NS100 SERVOPACKs, so the Gain Switch cannot be used.
When SGDV SERVOPACKs are used and the tuning-less function is available, this setting is ignored.

0: Gain switch OFF (default)
1: Gain switch ON

Bit 5

Gain Switch 2 (Valid with SVB-01 version 1.20 or later and built-in SVB version 2.50 or later)

0: Gain switch OFF (default)
1: Gain switch ON

Can be used only when using an SGDS SERVOPACK. (Not available for SGDV SERVOPACKs.)
In combination with bit 4, four types of gain switches can be set.

Bit6

Latch Mode Selection

0: Usual latch
1: Continuous latch

Available only for SGDV SERVOPACKs.

Position

Phase

Speed Torque

Register No.

Name

Setting Range Default Value

Meaning

Description

OW

00

RUN

Command

Setting

Bit setting

0

Bit 4: Latch Detection
Demand

0: OFF 1: ON

Bit 13: Latch Completion
Status Clear Request

0: OFF 1: ON

OW

01

Mode

Setting 1

Bit setting

0

Bit 6: Latch Mode Selection

0: Usual latch
1: Continuous latch

OW

04

Function
Setting 2

2 to 5

3

Bits 0 to 3: Latch Detection
Signal Selection

2: Phase-C pulse input signal
3: /EXT1
4: /EXT2
5: /EXT3

Advertising