10.3 Main Commands and Subcommands

10.3.3 Command Details

10-15

Settings for Connecting Inverters

10.3.3 Command Details

Each command and its parameters are described below.

( 1 ) No Command

Description

No command to be executed

Setting Parameters

Monitoring Parameters

( 2 ) Inverter Drive Control

Description

Sends commands to the Inverter and monitors the Inverter.

If the command Inverter Drive Control is switched to another command during its execution, the Inverter retains the
last data and continues operation. The MPE720 retains the last data of the monitoring parameters since inputs and
outputs between SVB Module and Inverter are stopped. The monitoring parameter Status, however, will be updated
for any command being executed except Transmission Reference.

Setting Parameters

Name

Register No.

Setting Range

Remarks

Command Code

OW

08

0 to 8

00: No Command

Name

Register No.

Setting

Range

Remarks

Command Response Code

IW

08

0 to 8

00: No Command

Command Status

IW

09

Bit

Bit 0 (Command execution flag)

Always OFF

Bit 3 (Command error completed
status)

On when an error
occurs during command
processing.

Bit 8 (Command execution com-
pleted status)

ON when command
execution is completed.

Status

IW

10

Bit

Inverter status

Response Alarm Code

IW

30

0 to FFFFH

Inverter alarm code

Name

Register No.

Setting Range

Remarks

Command Code

OW

08

0 to 8

01: Inverter Drive Control

Output Data Option Selection

OW

0C

Bit 0 to 3

Input Data Option Selection

OW

0D

Bit 0 to C

Input Command

OW

10

Bit

Frequency Reference

OW

11

Torque Reference

OW

12

Torque Compensation

OW

13

Valid when the Output Data Option Selection
(OW

0C), bit 0 is ON.

Multi-function Analog Output
FM (Option)

OW

14

Valid when the Output Data Option Selection
(OW

0C), bit 1 is ON.

Multi-function Analog Output
AM (Option)

OW

15

Valid when the Output Data Option Selection
(OW

0C), bit 2 is ON.

Multi-function Terminal
Output

OW

16

Valid when the Output Data Option Selection
(OW

0C), bit 3 is ON.