9.3 Absolute Position Detection for Finite Length Axes

9.3.2 Setting the Zero Point for a Finite Length Axis

9-10

( 3 ) Saving OL

48 Values before Power OFF

After having set the zero point, save the value of OL

48 before turning OFF the power of Machine Controller so

that the value will be written in OL

48 the next time the power is turned ON.

There are two ways to save the Zero Point Position in Machine Coordinate System Offset (OL

48) value. It can be

saved through a ladder program in an M Register backed up by battery or from the MPE720 Parameter Window. These
ways are described below.

Method 1: Saving the Zero Point Position in Machine Coordinate System Offset (OL

48) from

the MPE720 Parameter Window

Open the Parameter Window for the specified axis on the MPE720 and use the following procedure to save the Zero
Point Offset.

1.

Check the value in IL

10 in the Monitor Tab Page.

2.

Check the current value in OL

48 in the Setup Parameters Tab Page. Subtract the Calculated Posi-

tion (IL

10) from the Zero Point Position in Machine Coordinate System Offset (OL

48) and save

the result in OL

48.

3.

Check to see if the setting and current value in OL

48 are the same. If they are the same, select

File - Save and save the setting to the Machine Controller.

4.

Return to Module Configuration Window and select Save - Save to Flash to save the setting in the
flash memory.

5.

Execute the setting with the ZSET command.

When the power is turned ON, the value that was saved will be stored automatically for Zero Point Position in Machine
Coordinate System Offset (OL

48).