2 inverter warnings – Yaskawa MP2000 Series: Built-in SVB or SVB-01 Motion Module User Manual

Page 413

Advertising
background image

10.5 Inverter Alarm and Warning Codes

10.5.2 Inverter Warnings

10-49

Settings for Connecting Inverters

10.5.2 Inverter Warnings

−: Unchanged, ON: The corresponding bit turns ON, : Supported, ×: Not supported

Alarm Code

(IW

30)

Status (IW

10)

Digital

Operator

Display

Contents

V

a

rispeed

G7

V

arispee

d F7

VSmini

V7

WARNG

ALM

01H

ON

UV

Main circuit undervoltage

02H

ON

OV

Overvoltage

03H

ON

OH

Inverter overheat

04H

ON

OH2

Inverter overheat

×

05H

ON

OL3

Overtorque 1

06H

ON

OL4

Overtorque 2

×

07H

ON

EF

External fault

08H

ON

BB

Externally baseblocked

09H

ON

EF3

External fault 3

×

0AH

ON

EF4

External fault 4

×

0BH

ON

EF5

External fault 5

×

0CH

ON

EF6

External fault 6

×

0DH

ON

EF7

External fault 7

×

0EH

ON

EF8

External fault 8

×

0FH

ON

FAN

Cooling fan fault

×

×

10H

ON

OS

Excessive Speed

×

11H

ON

DEV

Excessive speed deviation

×

12H

ON

PGO

PG disconnected

×

13H

ON

OPR

Operator disconnected

14H

ON

CE

MEMOBUS transmission error

17H

ON

OL1

Motor overload

×

18H

ON

OL2

Inverter overload

×

1AH

ON

EFO

External fault

×

1BH

ON

RUN

Motor running

×

1CH

ON

FBL

PID feedback reference loss

1DH

ON

CALL

Waiting for transmission data

1EH

ON

UL3

Undertorque 1

1FH

ON

UL4

Undertorque 2

×

20H

ON

SER

Sequence input error

×

×

22H

ON

OH3

Motor overheated 1

×

23H

ON

EF9

External fault 9

×

24H

ON

EF10

External fault 10

×

25H

ON

EF11

External fault 11

×

26H

ON

EF12

External fault 12

×

40H

ON

STP

Emergency stop

×

×

41H

ON

STP

Urgent stop

×

×

Advertising