6.2 Motion Command Details

6.2.20 Clear Alarm History (ALMHIST_CLR)

6-76

6.2.20 Clear Alarm History (ALMHIST_CLR)

The ALMHIST_CLR command clears the alarm history in the SERVOPACK.

( 1 ) Executing/Operating Procedure

1.

Check to see if all the following conditions are satisfied.

2.

Set OW

08 to 21 to execute the ALMHIST_CLR motion command.

The ALMHIST_CLR command will clear the alarm history stored in the SERVOPACK.
IW

08 will be 21 during command execution.

IW

09, bit 0 will turn ON during the command processing and will turn OFF when the command processing

has been completed.

3.

Set OW

08 to 0 to execute the NOP motion command and then clear the alarm history.

( 2 ) Holding and Aborting

The Holds a Command bit (OW

09, bit 0) and the Interrupt a Command bit (OW

09, bit 1) cannot be used.

( 3 ) Related Parameters

[ a ] Setting Parameters

[ b ] Monitoring Parameters

No.

Execution Conditions

Confirmation Method

1

Motion command execution has been completed.

IW

08 is 0 and IW

09, bit 0 is OFF.

Parameter

Name

Setting

OW

08

Motion Command

The alarm history is cleared when this parameter is set to 21.

OW

09

Bit 0

Holds a Command

This parameter is ignored for ALMHIST_CLR command.

OW

09

Bit 1

Interrupt a Command

This parameter is ignored for ALMHIST_CLR command.

Parameter

Name

Monitor Contents

IL

02

Warning

Stores the most current warning.

IL

04

Alarm

Stores the most current alarm.

IW

08

Motion Command
Response Code

Indicates the motion command that is being executed.
The response code will be 21 during ALMHIST_CLR command execution.

IW

09

Bit 0

Command Execution
Flag

Turns ON during ALMHIST_CLR command execution and turns OFF when execution
has been completed.

IW

09

Bit 1

Command Hold
Completed

Always OFF for ALMHIST_CLR command.

IW

09

Bit 3

Command Error
Completed Status

Turns ON if an error occurs during ALMHIST_CLR command execution.
Turns OFF when another command is executed.

IW

09

Bit 8

Command Execution
Completed

Turns ON when ALMHIST_CLR command execution has been completed.