12.2 Troubleshooting System Errors

12.2.2 Troubleshooting Flowchart for System Errors

12-9

Troubleshooting

12.2.2 Troubleshooting Flowchart for System Errors

A troubleshooting flowchart for system errors is provided below.

* For LED indicator pattern, refer to 12.1.3 ( 2 ) LED Indicator Meanings.

START

YES

NO

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

Use the LED indicator

pattern

*

to classify the

error.

Classifications = Warning

ALM indicator lit or

blinking?

Classifications = Fatal error

ERR indicator blinking?

Hardware failure/watchdog timer timeout

Only ERR indicator lit?

Turn OFF the STOP switch on

DIP siwtch SW6 and turn ON the

power.

Online Stop Mode

Only RDY indicator lit?

Check SW00050.

Watchdog timer timeout?

User program error

Hardware

failure

Check CPU Error Status (SW00041).

User program

error

Battery alarm

indicator

BAT lit?

Replace battery.

Fatal error

Alarm

Check the location of the error
referring to 12.2.3 Correcting
User Program Errors
.

(1) Operation error (SB000418)

Refer to 12.2.4 ( 3 ) Ladder Program User Opera-
tion Error Status
.

(2) I/O error (SB000419)

Refer to 12.2.4 ( 6 ) System I/O Error Status.