6.2 Motion Command Details

6.2.13 Change Speed Loop Gain (KVS)

6-62

6.2.13 Change Speed Loop Gain (KVS)

The KVS command transfers the setting of the Speed Loop Gain (motion setting parameter OW

2F) to the Speed

Loop Gain in the SERVOPACK and enables the setting.

MECHATROLINK-II has a function that automatically updates setting parameters if a parameter changes. There is
no need to execute the KVS command with this function. For details, refer to bit A (User Constants Self-writing Func-
tion) in 4.4.1 ( 2 ) Function Selection 1.

( 1 ) Executing/Operating Procedure

1.

Check to see if all the following conditions are satisfied.

2.

Set OW

08 to 14 to execute the KVS motion command.

The KVS command will transfer the setting of the Speed Loop Gain (motion setting parameter OW

2F) to the

Speed Loop Gain in the SERVOPACK and enables the setting.
IW

08 will be 14 during command execution.

IW

09, bit 0 will turn ON during the command processing and will turn OFF when the command processing

has been completed.

3.

Set OW

08 to 0 to execute the NOP motion command and then complete the change of the speed

loop gain.

( 2 ) Holding and Aborting

The Holds a Command bit (OW

09, bit 0) and the Interrupt a Command bit (OW

09, bit 1) cannot be used.

When the tuning-less function of the SGDV SERVOPACK is enabled or when the SERVOPACK parameter Pn170.0 is
set to 1 (Tuning-less Function Selection is enabled), these settings are disabled and ignored.

( 3 ) Related Parameters

[ a ] Setting Parameters

[ b ] Monitoring Parameters

No.

Execution Conditions

Confirmation Method

1

There are no alarms.

Both IL

02 and IL

04 are 0.

2

Motion command execution has been completed.

IW

08 is 0 and IW

09, bit 0 is OFF.

Parameter

Name

Setting

OW

08

Motion Command

The speed loop gain is changed when this parameter is set to 14.

OW

09

Bit 0

Holds a Command

This parameter is ignored for KVS command.

OW

09

Bit 1

Interrupt a Command

This parameter is ignored for KVS command.

OW

2F

Speed Loop Gain

Set the gain for the SERVOPACK speed control loop.

Parameter

Name

Monitor Contents

IL

02

Warning

Stores the most current warning.

IL

04

Alarm

Stores the most current alarm.

IW

08

Motion Command
Response Code

Indicates the motion command that is being executed.
The response code will be 14 during KVS command execution.

IW

09

Bit 0

Command Execution
Flag

Turns ON during KVS command execution and turns OFF when execution has been
completed.

IW

09

Bit 1

Command Hold
Completed

Always OFF for KVS command.

IW

09

Bit 3

Command Error
Completed Status

Turns ON if an error occurs during KVS command execution.
Turns OFF when another command is executed.