6.2 Motion Command Details

6.2.26 Stored Parameter Write (PPRM_WR)

6-96

[ b ] Monitoring Parameters

( 4 ) Timing Diagram

[ a ] Normal End

[ b ] Error End

Parameter

Name

Monitor Contents

IL

02

Warning

Stores the currently occurring warning.

IL

04

Alarm

Stores the currently occurring alarm.

IW

08

Motion Command
Response Code

Indicates the motion command that is being executed.
The response code will be 27 during execution of the PPRM_WR command.

IW

09

Bit 0

Command Execution
Execution Flag

ON during PPRM_WR command execution. Turns OFF when the execution is com-
pleted.

IW

09

Bit 1

Command Hold
Completed

Always OFF for PPRM_WR command.

IW

09

Bit 3

Command Error
Completed Status

Turns ON when an error occurs during PPRM_WR command execution.
Turns OFF when another command is executed.

IW

09

Bit 8

Command Execution
Completed

Turns ON when PPRM_WR command execution has been completed.

OW

08 = 27 (PPRM_WR)

IW

08 = 27 (PPRM_WR)

IW

09, bit 0 (BUSY)

Undefined length

of time

IW

09. bit 8 (COMPLETE)

IW

09, bit 3 (FAIL)

Undefined length

of time

OW

08=27(PPRM_WR)

IW

08=27(PPRM_WR)

IW

09, bit 0 (BUSY)

IW

09, bit 8 (COMPLETE)

IW

09, bit 3 (FAIL)

Advertising