3 ) setting procedure – Yaskawa MP2000 Series: Built-in SVB or SVB-01 Motion Module User Manual

Page 434

Advertising
background image

11.5 Bank Switching Function

11.5.4 Bank Member Setting

11-19

Utility Functions

( 3 ) Setting Procedure

1.

Set the Number of Parameter Banks (Pn900) and Number of Parameter Bank Members (Pn901).

Number of Parameter Banks and Number of Parameter Bank Members must satisfy the following equation.
Number of Parameter Banks

× Number of Parameter Bank members

64

2.

Register the parameters to be Bank Members in the parameters Pn902 through Pn910.

3.

Set each bank data in the parameter bank data area starting from Pn920. (See the following Setting
Example
.)

4.

Turn OFF the power to the SERVOPACK and then turn ON again.

Setting Example: Three Banks with Members Pn80B, Pn80E, and Pn80C

The Bank Number starts from 0 (zero).
Set above bank numbers in the Machine Controller’s motion setting parameter Bank Selector (OW

04, bits

C to F).

Pn900 = 3

Number of Banks

Pn901 = 3

Number of Members

Pn902 = 80BH

Member 1

Pn903 = 80EH

Pn904 = 80CH

Member 3

Member 2

Bank 0

Pn920 = 80BH value (0)

Pn921 = 80EH value (0)

Pn922 = 80CH value (0)

Pn923 = 80BH value (1)

Pn924 = 80EH value (1)

Pn925 = 80CH value (1)

Pn926 = 80BH value (2)

Pn927 = 80EH value (2)

Pn928 = 80CH value (2)

Bank 1

Bank 2

Bank Number