10.5 Inverter Alarm and Warning Codes

10.5.3 Communication Warnings

10-50

10.5.3 Communication Warnings

−: Unchanged, ON: The corresponding bit turns ON, : Supported

10.5.4 Communication Alarm

−: Unchanged, ON: The corresponding bit turns ON, : Supported

10.5.5 Optional Interface Settings

The hardware switch settings for SI-T and SI-T/V7, which are MECHATROLINK-I and -II communication optional
boards for general-purpose inverter Varispeed F7, Varispeed G7, and VSminiV7, are described below.

( 1 ) S1: DIP Switches

Alarm Code

(IW

30)

Status (IW

10)

Digital

Operator

Display

Contents

V

ar

ispeed G7

V

ar

ispeed F

7

VSmi

niV7

WARNG

ALM

94H

ON

Data setting warning

95H

ON

Command warning

96H

ON

MECHATROLINK

-

II communica-

tion error warning

Alarm Code

(IW

30)

Status (IW

10)

Digital

Operator

Display

Contents

V

arispe

ed G7

V

arisp

eed F7

VS

m

in

iV

7

WARNG

ALM

E5H

ON

E5

MECHATROLINK

-

II WDT

timeout error

E6H

ON

BUS

MECHATROLINK-II
communication error

ECH

ON

WDC timeout error in
communication with Inverter

EDH

ON

Inverter access permission error

EEH

ON

Inverter watchdog timeout

Device

Code

Switch Name

Status

Description

S1-1

BRS10/4

OFF

4 Mbps

ON

10 Mbps

S1-2

BYTE16/31

OFF

17-byte transmission mode
(For MECHATROLINK-I and MECHATROLINK-II 17-byte mode only)

ON

32-byte transmission mode
(For MECHATROLINK-II 32-byte mode only)

S1-3

SA16/32

OFF

Sets the second digit of the station address to 0 in hexadecimal.
For MECHATROLINK communications, sets it to 2.
Note: The station address 00 or 20, in which the two digits are set by the

S1-3 DIP switch and the S2 rotary switch, is invalid.

ON

Sets the second digit of the station address to 1 in hexadecimal.
For MECHATROLINK communications, sets it to 3.
Note: The station address 1F or 3F, in which the two digits are set by the

S1-3 DIP switch and the S2 rotary switch, is invalid.

S1-4

TEST

OFF

Normal mode

ON

Diagnosis mode