4.4 MP2000 Series Machine Controller Parameter Details
4.4.2 Motion Setting Parameter Details
4-30
[ b ] Details of Latch Operations
Usual Latch Operation
Check the completion of the latch with bit 2 of IW
0C.
To repeat latching again, set bit 4 of OW
00 to 1.
<Example>
• Condition: Latch at phase-C pulse
• Settings:
Motion setting parameters
Servo parameters
Pn850 Setting
Latch Operation
Latch Single Setting
= 0
– (Error)
–
> 0
Continuous Latch Operation
Setting with Pn852 and Pn853
Latch Detection Demand
OW
00.bit 4
Continuous Latch Mode
= 1
Continuous Latch Operation
(Latch signals are set in Pn852 and Pn853.)
Setting Error
(Warning in SERVOPACK)
Usual Latch Operation
(Latch signals are set in bits 0 to 3
of OW
04.)
Usual Latch Mode
OW
01.bit 6
= 0
> 0
= 0
Register No.
Name
Setting value
OW
01
Mode Setting 1
Bit 6: Latch mode selection = 0 (usual latch)
OW
04
Function Setting 2
Bits 0 to 3: Latch Detection Signal Selection = 2 (Phase-C pulse)
Parameter No.
Name
Setting value
Pn850
Latch Sequence Number
Disabled
Pn851
Continuous Latch Count
Disabled
Pn852
Latch Sequence Signal 1 to 4 Setting
Disabled
Pn853
Latch Sequence Signal 5 to 8 Setting
Disabled