6.2 Motion Command Details

6.2.24 Phase References (PHASE)

6-91

Motion Commands

( 4 ) Timing Charts

[ a ] Normal Execution

[ b ] Execution when Aborted

IW

0C

Bit 0

Discharging Completed

Turns ON when pulse distribution has been completed for the move com-
mand.
Turns OFF during execution of a move command.

IW

0C

Bit 1

Positioning Completed

Turns ON when pulse distribution has been completed and the current posi-
tion is within the width of Positioning Completion. OFF in all other cases.

IW

0C

Bit 3

NEAR Position

The operation of this bit depends on the setting of NEAR Signal Output
Width (setting parameter OL

20).

OL

20 = 0:Turns ON when pulse distribution has been completed

(DEN = ON). Otherwise, it turns OFF.

OL

20

0:Turns ON when the absolute value of the difference

between MPOS (IL

12) and APOS (IL

16) is less

than the NEAR Signal Output Width, even if pulse distribu-
tion has not been completed.
OFF in all other cases.

(cont’d)

Parameter

Name

Monitor Contents

SVR

R

R

R

OW

08 = 25 (PHASE)

IW

08 = 25 (PHASE)

IW

09, bit 0 (BUSY)

IW

09, bit 8 (COMPLETE)

IW

09, bit 3 (FAIL)

IW

0C, bit 0 (DEN)

IW

0C, bit 1 (POSCOMP)

Undefined length of time

1 scan

The Target Position is automatically refreshed every scan.

Undefined length of time

IW

0C, bit 1 (POSCOMP)

1scan

OW

08=25(PHASE)

IW

09, bit 0 (BUSY)

IW

08=25(PHASE)

IW

09, bit 3 (FAIL)

IW

0C, bit 0 (DEN)

IW

09, bit 8 (COMPLETE)

The Target Position is automatically refreshed every scan.